EasyManua.ls Logo

Daikin WGZ030DW - Page 29

Daikin WGZ030DW
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OMM 1130-2 29
High Condenser Pressure - Unload
Event description (as shown on screen): CondPressHighUnloadN
Trigger:
This event is triggered if all of the following are true:
• circuit state = Run
• more than one compressor is running on the circuit
• condenser pressure > High Condenser Pressure – Unload set point
Action Taken: Stage off one compressor on the circuit every 10 seconds, except the last one.
Reset: While still running, the event will be reset if condenser pressure drops below the “Hold Clear @”
value which is displayed on that circuit’s VIEW CIRCUIT n (1) screen. The “Hold Clear @” is calculated
based on number of compressors, refrigerant, and number of High Condenser Pressure – Unload
occurrences since the circuit has cycled off or since midnight. See table below:
Condenser
Configuration
Compressors R410A
R22
R407C
R134a
Step
Increase
Water-Cooled
4 40 psi 30 psi 30 psi 10 psi
6 30 psi N/A 20 psi 10 psi
Air-Cooled
4 100 psi 70 psi N/A 15 psi
6 80 psi N/A N/A 15psi
Failed Pumpdown
Event description (as shown on screen): Pumpdown Fail Cir N
Trigger: Circuit state = pumpdown for time > 60 seconds
Action Taken: Shutdown circuit
Reset: N/A
Condenser Freeze Event
Event description (as shown on screen): Cond Freeze Circ N
Trigger: Cond Sat Refr Temperatre < Condenser Freeze Set Point AND Condenser Pump State = OFF
Action Taken: Start condense pump.
Reset: N/A
Condenser Freeze Event (Water Cooled = Y Only)
Event description (as shown on screen): Cond Freeze Circ N
Trigger: Cond Sat Refr Temp < Condenser Freeze Set Point AND Condenser Pump State = OFF
Action Taken: Start condenser pump.
Reset: Cond Sat Refr Temp > Condenser Freeze Set Point plus 2°F.
Suction Temperature Sensor Fail
Event description (as shown on screen): SuctT Sensor Fail N
Trigger: Sensor shorted or open.
Action Taken: None.
Reset: N/A
Entering Evaporator Water Temperature Sensor Fail (TGZ unit only)
Event description (as shown on screen): Evap EWT Sensor Fail
Trigger: Sensor shorted or open.
Action Taken: None.
Reset: N/A