OMM 1130-2 61
SET UNIT SPs (4)
Start Delta= XX.X°F
Stop Delta= XX.X°F
Demand Limit = ON
See page 13 for an explanation of compressor staging.
WGZ Units Only TGZ Units Only (R134a)
SET UNIT SPs (5)
Max Pulldn=X.X
°
F/min
Evap Recirc= XXX sec
Evap Pump = #1 Only
SET UNIT SPs (5)
Max Pulldn=X.X
°
F/min
Evap Recirc= XXX sec
Evap Pump = #1 Only
Evap Pump choices are; #1 Only, #2 Only, Auto, #1 Primary, #2 Primary.
Water-Cooled = ON Water-Cooled = OFF
SET UNIT SPs (6)
SET UNIT SPs (6)
Water Cooled = ON
Water Cooled = Off
Cond Recirc=XXX sec
LowAmbLock XXX.X °F
Cond Pump = #1 Only
TGZ Units (R134a)
SET UNIT SPs (6)
Water Cooled = Off
LowAmbLock XXX.X °F
Water Cooled = On is the setting for units with on-board water-cooled condensers. Pump choices are;
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary.
WaterCooled = OFF is used for units with remote condensers, usually air cooled.
SET UNIT SPs (7)
Ice Time Delay=Xxsec
Clear Ice Delay=No
H.G. Delay = XX sec
H.G. Delay, hot gas bypass delay, keeps the hot gas solenoid valve closed when the first compressor on a
circuit starts. This delay allows sufficient condenser pressure to build up.
SET UNIT SPs (8)
CLOCK
dd/mmm/yyyy
hh:mm:ss
SET UNIT SPs (9)
SET UNIT SPs (9)
SET UNIT SPs (9)
Units = °F/psi
Units = °F/psi
Units = °F/psi
Lang = ENGLISH
Lang = ENGLISH
Lang = ENGLISH
Refrig = None
Refrig = R22
Refrig = R407C