VLT
®
MICRO
Pr.24 Reverse Run Inhibit
Factory Setting d00
Units None
Settings d00 REV run enabled
d01 REV run disabled
This parameter inhibits AC drive operation in the reverse direction.
Pr.25 Over-voltage Stall Prevention
Factory Setting d01
Units None
Settings d00 Disable over-voltage stall prevention
d01 Enbable over-voltage stall prevention
During deceleration, the DC bus voltage may exceed the maximum amount allowable
due to motor regeneration. When this function is enabled, the AC drive will cease to
decelerate and then maintain a constant output frequency. The drive will only resume
deceleration when the voltage drops below the preset value.
Pr.26, Pr.27 Over-Current Stall Prevention
Pr.26 Over-Current Stall Prevention During Acceleration
Factory Setting d170%
Units 1%
Parameter value d50 - d200%
Over voltage stall prevention
Time
Time
Output
frequency
DC bus
voltage
Over voltage
detection
level
28