30 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Refrigerant setting:
1=R12.2=R22.3=R134a.4=R502.5=R717.6=R13.
7=R13b1.8=R23.9=R500.10=R503.11=R114.
12=R142b.13=Userdened.14=R32.15=R227.
16=R401A.17=R507.18=R402A.19=R404A.20=R407C.
21=R407A.22=R407B.23=R410A.24=R170.25=R290.
26=R600.27=R600a.28=R744.29=R1270.30=R417A.
31=R422A.
o30 1 1 1 1 1 1 1 1 1 1 0 31 0
InputsignalonDI2.Function:
(0=notused.1=statusonDI2.2=doorfunctionwithalarm
whenopen.3=dooralarmwhenopen.4=defroststart
(pulse-signal).5=ext.mainswitch6=nightoperation
7=thermostatbandchangeover(activater21).8=alarm
functionwhenclosed.9=alarmfunctionwhenopen.
10=casecleaning(pulsesignal).11=forcedcoolingathot
gasdefrost.).12=nightcover,13=coordinateddefrost)
o37 1 1 1 1 1 1 1 1 1 1 0 13 0
Congurationoflightfunction:1=Lightfollowsday/night
operation,2=Lightcontrolviadatacommunication
via‘o39’,3=LightcontrolwithaDI-input,4=As"2",but
lightswitchonandnightcoverwillopenifthenetwork
cut out for more than 15 minutes.
o38 1 1 1 1 1 1 1 1 1 4 1
Activationoflightrelay(onlyifo38=2)On=light o39 1 1 1 1 1 1 1 1 0/O 1/On 0/O
RailheatOntimeduringdayoperations
o41 1 1 1 1 1 1 1 0% 100% 100
RailheatOntimeduringnightoperations
o42 1 1 1 1 1 1 1 0% 100% 100
Railheatperiodtime(Ontime+Otime)
o43 1 1 1 1 1 1 1 6min. 60min. 10
Casecleaning.0=nocasecleaning.1=Fansonly.2=All
outputO.
*** o46 1 1 1 1 1 1 1 1 1 1 0 2 0
SelectionofELdiagram.Seeoverviewpage12and13
* o61 1 1 1 1 1 1 1 1 1 1 1 10 1
Downloadasetofpredeterminedsettings.Seeoverview
page27.
* o62 1 1 1 1 1 1 1 1 1 1 0 6 0
Accesscode2(partialaccess)
*** o64 1 1 1 1 1 1 1 1 1 1 0 100 0
Replace the controllers factory settings with the present
settings
o67 1 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
InputsignalonDI3.Function:(highvoltageinput)
(0=notused.1=statusonDI2.2=doorfunctionwithalarm
whenopen.3=dooralarmwhenopen.4=defroststart
(pulse-signal).5=ext.mainswitch6=nightoperation,
7=thermostatbandchangeover(activater21). 8=Not used.
9=Notused.10=casecleaning(pulsesignal).11=forced
cooling at hot gas defrost, 12=nightcover.13=Notused.
14=Refrigerationstopped(forcedclosing))
o84 1 1 1 1 1 1 1 1 1 1 0 14 0
Rail heat control
0=notused,1=pulsecontrolwithtimerfunction(o41
ando42),2=pulsecontrolwithdewpointfunction
o85 1 1 1 1 1 1 1 0 2 0
Dewpointvaluewheretherailheatisminimum o86 1 1 1 1 1 1 1 -10°C 50°C 8
Dewpointvaluewheretherailheatis100%on o87 1 1 1 1 1 1 1 -9°C 50°C 17
Lowestpermittedrailheateectin% o88 1 1 1 1 1 1 1 0% 100% 30
Timedelayfrom"opendoor”refrigerationisstarted o89 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 30
Fanoperationonstoppedrefrigeration(forcedclosing):
no/0=FanO,yes/1=FanOn
o90 1 1 1 1 1 1 1 1 1 1 0/no 1/yes 1/yes
Denitionofreadingsonlowerbutton:
1=defroststoptemperature,2=S6temperature,
3=S5_Btemperature
o92 1 1 1 1 1 1 1 1 1 1 1 3 1
Display of temperature
1=u56Airtemperature
2=u36producttemperature
o97 1 1 1 1 1 1 1 1 1 1 1 2 1
Lightandnightblindsdened
0:Lightisswitchoandnightblindisopenwhenthe
mainswitchiso
1:Lightandnightblindisindependentofmainswitch
o98 1 1 1 1 1 1 1 1 1 1 0 1 0
Congurationofalarmrelay
Thealarmrelaywillbeactivateduponanalarmsignal
from the following groups:
1-Hightemperaturealarms
2-Lowtemperaturealarms
4-Sensorerror
8-Digitalinputisactivatedforalarm
16-Defrostalarms
32-Miscellaneous
64-Injectionalarms
Thegroupsthataretoactivatethealarmrelaymustbe
setbyusinganumericalvaluewhichisthesumofthe
groupsthatmustbeactivated.
(E.g.avalueof5willactivateallhightemperature
alarmsandallsensorerrors)
P41 1 1 1 1 1 0 127 111