AKD 2800
All about AKD
2800
Calculations are taking too long, possibly due
to noise on the motor cables.
ALARM 56: AMT warning during AMT
A frequency converter warning is given while
AMT is being performed.
WARNING 99: Locked
See parameter 18.
Alarm/warning limits:
Without brake With brake Without brake With brake
AKD 2800 1 / 3 x 200 - 240 V
[VDC]
1 / 3 x 200 - 240 V
[VDC]
3x380-480V
[VDC]
3 x 380 - 480 V
[VDC]
Undervoltage 215 215 410 410
Voltage warning low 230 230 440 440
Voltage warning high 385 400 765 800
Overvoltage 410 410 820 820
Thevoltagesstatedaretheintermediatecircuit
voltage of the frequency converter with a tolerance
of ± 5 %. The corresponding line voltage is the
intermediate circuit voltage divided by 1,35.