Total stop 5021
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop during the setback temperature period.
ON: The desired system temperature is lowered to ‘Standby T’ (line 7093).
‘Temp. min.’ (line 2177) is overruled.
Desired system temp. °C
‘Standby T’
Time
OFF: No total stop
Desired system temp. °C
‘Standby T’
Time
S1 T filter (outdoor temp. filter) 5081
Setting range Factory setting
1 ... 200 100
Dampens the measured outdoor temperatures by the set factor.
1: Fast (low filter constant)
200: Slow (high filter constant)
Cut-out (limit for heating cut-out) 5179
Setting range Factory setting
OFF / 1 ... 50 °C 18 °C
Set the outdoor temperature limit at which you want the heating system to stop. The
valve closes and after about 3 min. the heating circulation pump stops. ‘Temp. min.’
set in line 2177 will be ignored.
Temp. Actual outdoor temp. Accumulated outdoor temp.
Time
Heating Heating OFF Heating
This function can save energy by stopping the heating system when the outdoor
temperature gets above a set limit. The heating system switches ON again when the
outdoor temperature and the accumulated outdoor temperature become lower than
the set limit.
The heating cut-out is only active when the controller mode is AUTO (scheduled operation).
When the limit value is set to OFF, there is no heating cut-out.