30 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK
DH-SMT/DK VI.KT.G2.02 © Danfoss 05/2007 31
DHW prior. (closed valve / normal operation) 7052
Setting range Factory setting
ON / OFF OFF
The heating circuit can be closed when the controller acts as slave and when DHW charging is active in
the master.
ON: The valve in the heating circuit is closed* during active DHW charging in
the master controller.
* The desired flow temperature is set to ‘Standby T’ (line 7093)
OFF: The flow temperature control remains unchanged during active DHW
charging in the master controller.
The setting in line 7052 must be considered if this controller is a slave.
P1 frost T (frost protection) 7077
Setting range Factory setting
OFF / -10 ... 20 °C 2 °C
When the outdoor temperature is below the set temperature in ‘P1 frost T’, the controller automatically
switches ON the circulation pump to protect the system.
OFF: No frost protection.
-10 ... 20:
The circulation pump is ON when the outdoor temperature is below
the set value.
Under normal conditions, your system is not frost protected if your setting is below 0 °C or
OFF. For water-based systems, a setting of 2 °C is recommended.
P1 heat T (heat demand) 7078
Setting range Factory setting
5 ... 40 °C 20 °C
When the desired flow temperature is above the set temperature in ‘P1 heat T’, the controller
automatically switches ON the circulation pump to meet the heat demand.
5 ... 40:
The circulation pump is ON above the set value.
The valve is fully closed as long as the pump is not switched on.
Standby T (standby temperature) 7093
Setting range Factory setting
5 ... 40 °C 10 °C
Set the desired flow temperature at standby (e.g. during total stop).
5 ... 40:
Desired standby flow temperature.
Ext. (external override) 7141
Setting range Factory setting
OFF / SETBACK / COMFORT OFF
Choose mode for ‘Ext.’ (external override).
The override can be activated for setback or comfort mode. For override, the controller
mode must be AUTO (scheduled operation).
OFF: The controller's schedule is not overridden.
SETBACK:
The controller is in setback mode when terminals 11 and 12 are short-
circuited.
COMFORT:
The controller is in comfort mode when terminals 11 and 12 are short-
circuited.

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals