28 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK
DH-SMT/DK VI.KT.G2.02 © Danfoss 05/2007 29
If you want to tune the PI regulation precisely, you can use the following
method:
Set the ‘Tn’ (integration time constant line 6185) to its max. value (999 sec.).
Decrease the value for the ‘Xp’ (proportional band line 6184) until the system starts
hunting with a constant amplitude (it might be necessary to force the system by setting
an extreme value).
Find the critical time period on the temperature recording or use a stop watch.
Temp. Critical time period
Time
This time period will be characteristic for the system, and you can evaluate the settings from
this critical period.
‘Tn’ = 0.85 x critical time period
‘Xp’ = 2.2 x proportional band value in the critical time period.
If the regulation seems to be too slow, you can decrease the proportional band value by
10%.
ECA address (choice of room panel / remote control) 7010
Setting range Factory setting
OFF / A / B OFF
Decides the communication with the room panel or remote control.
OFF: Room temperature sensor (no room panel / remote control)
A: Room panel ECA 60 / 62 or remote control, ECA 61 / 63 with address A
B: Room panel ECA 60 / 62 or remote control, ECA 61 / 63 with address B
P1 exercise (pump exercise) 7022
Setting range Factory setting
ON / OFF ON
Exercises the pump to avoid blocking in periods without heat demand.
ON: The pump is switched ON for 1 minute every third day around noon.
OFF: The pump exercise is not active.
M1 exercise (valve exercise) 7023
Setting range Factory setting
ON / OFF OFF
Exercises the valve to avoid blocking in periods without heat demand.
ON: The valve receives a signal to open and close every third day around
noon.
OFF: The valve exercise is not active.
Actuator (gear motor / thermo actuator) 7024
Setting range Factory setting
GEAR / ABV GEAR
Choose the actuator type for your valve.
GEAR: Gear motor
ABV: Thermo actuator (Danfoss type ABV)
Control parameters (lines 6174-6187) are overruled if thermo actuator is chosen (ABV).
Application 7000

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals