Maintenance
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example: 5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example: 90 degr. x 2 sec. / degr. = 180 sec.
Nz (neutral zone) 6187
Setting range Factory setting
1 ... 9 K 3 K
Set the acceptable ow temperature deviation.
Set the neutral zone to a high value if you can accept a high variation in ow
temperature. When the actual ow temperature is within the neutral zone, the controller
does not activate the motorized control valve.
The neutral zone is symmetrical around the desired ow temperature value, i.e. half the
value is above and half the value is below this temperature.

Table of Contents

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
Communication ProtocolModbus RTU
Display TypeLCD
Mounting TypeDIN rail
Digital inputs4
Relay outputs2
Analog inputs2
Enclosure ratingIP20
Power Supply24 V AC or 24 V DC
Temperature Range0 to 50 °C
ApplicationHeating systems
InputsPt1000
OutputsRelay
Operating Temperature0 to 50 °C
Storage Temperature-20 to 60 °C

Related product manuals