Maintenance
Auto-reduct (setback temp. dependent on outdoor temp.) 5011
Setting range Factory setting
OFF / -29 ... 10 °C -15 °C
Below this outdoor temperature, the setback temperature setting has no inuence.
-29 ... 10: The setback temperature depends on the outdoor temperature, when
the outdoor temperature is above the set limit. The lower the outdoor
temperature, the less the temperature reduction. When the outdoor
temperature is below the set limit, there is no temperature reduction.
OFF: The setback temperature does not depend on the outdoor temperature.
Reduction
0%
-20 -10-29 02010
Outdoor
temp. °C
Setting line 5011
Boost 5012
Setting range Factory setting
OFF / 1 ... 99% OFF
Shortens the heating-up period by increasing the desired ow temperature by the percentage you set.
Set the percentage at which you want the desired ow temperature increased
temporarily.
In order to shorten the heating-up period after a setback temperature period, the desired
ow temperature can be increased temporarily (max. 1 hour). At optimizing the boost is
active in the optimization period (line 5014).
If a room temperature sensor or a room panel / remote control is connected, the boost
stops when the room temperature is reached.
Optimize 5000