VI.KT.G6.02
20 | © Danfoss | 2016.05
Maintenance
Auto-reduct (setback temp. dependent on outdoor temp.) 5011
Setting range Factory setting
OFF / -29 ... 10 °C -15 °C
Below this outdoor temperature, the setback temperature setting has no inuence.
-29 ... 10: The setback temperature depends on the outdoor temperature, when
the outdoor temperature is above the set limit. The lower the outdoor
temperature, the less the temperature reduction. When the outdoor
temperature is below the set limit, there is no temperature reduction.
OFF: The setback temperature does not depend on the outdoor temperature.
Reduction
100%
0%
-20 -10-29 02010
Outdoor
temp. °C
Setting line 5011
Boost 5012
Setting range Factory setting
OFF / 1 ... 99% OFF
Shortens the heating-up period by increasing the desired ow temperature by the percentage you set.
Set the percentage at which you want the desired ow temperature increased
temporarily.
In order to shorten the heating-up period after a setback temperature period, the desired
ow temperature can be increased temporarily (max. 1 hour). At optimizing the boost is
active in the optimization period (line 5014).
If a room temperature sensor or a room panel / remote control is connected, the boost
stops when the room temperature is reached.
Optimize 5000

Table of Contents

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals