Installation
* Optional connections for safety thermostat
Terminal Description Max.
load
20 Supply voltage 24 V a.c. - A1
21 Supply voltage 24 V a.c. - A2
22 Optional connections for safety thermostat
23 Optional connections for safety thermostat
24 M1 Actuator - open, alt. thermo actuator (ABV) 15 VA
25 M1 Actuator - close 15 VA
26 M1 Actuator - A1
27 Not to be used
28 Not to be used
29 P1 Phase for circulation pump (relay R2)
30 P1 Relay R2 4 (2) A
Wire cross section: 0.5 - 1.5 mm
2
Incorrect connection can damage the TRIAC outputs.
Electrical connections - 24 V a.c. - in general

Table of Contents

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
Communication ProtocolModbus RTU
Display TypeLCD
Mounting TypeDIN rail
Digital inputs4
Relay outputs2
Analog inputs2
Enclosure ratingIP20
Power Supply24 V AC or 24 V DC
Temperature Range0 to 50 °C
ApplicationHeating systems
InputsPt1000
OutputsRelay
Operating Temperature0 to 50 °C
Storage Temperature-20 to 60 °C