| 16 DKRCE.PI.RL0.F6.MLInstruction sheet | ERC 211
Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
High temperature alarm limit
(Cabinet/room)
A13 -100.0 200.0 C/F 8.0 16 10 10 80 8.0
Low temperature alarm limit A14 -100.0 200.0 C/F -30.0 0.0 0.0 0.0 10 -30.0
DI1 delay
(time delay for selected DI1 function)
A27 0 240 min 30 30 30 30 30 30
Condenser high alarm limit A37 0 200 C/F 80 80 80 80 - -
Condenser high block limit A54 0 200 C/F 85 85 85 85 - -
Voltage protection enable A72 no yES no no no no no no
Minimum cut-in voltage A73 0 270 V 0 0 0 0 0 0
Minimum cut-out voltage A74 0 270 V 0 0 0 0 0 0
Maximum voltage A75 0 270 V 270 270 270 270 270 270
Defrost d--
Defrost method
no=no defrost, nAt=natural
d01 no nAt no no nAt nAt no no
Defrost stop temperature d02 0.0 50.0 C/F 6.0 - - 8 - 6.0
Defrost interval d03 0 240 hours 8 - 6 6 - 8
Max defrost time d04 0 480 min 30 - 45 60 - 30
Defrost delay at power up
(or DI signal)
d05 0 240.0 min 0 - 0 0 - -
Drip delay d06 0 60 min 0 - 0 0 - -
Defrost stop sensor
configuration, non=time, Air=Sair (air temperature)
d10 non Air non - non Air - non
Compressor accumulated
runtime to start defrost, 0=OFF
d18 0 96 hours 0 - 0 0 - -
Defrost delay after pull-down
0=OFF
d30 0 960 min 0 - 0 0 - -
Compressor c--
Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0.0
Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2.0
Compressor OFF delay
at door open
C04 0 15 min 0 0 0 0 0 1
Zero crossing selection C70 no yES yES yES yES yES yES yES
Note: hidden parameters are greyed out
ENGLISH