| 17DKRCE.PI.RL0.F6.ML Instruction sheet | ERC 211
Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Others o--
Delay of outputs
at startup
o01 0 600 min 5 5 5 5 5 5
DI1 configuration
oFF=not used,
Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption,
SCH = main switch, nig=day/ night mode,
rFd=reference displacement,
EAL=external alarm,
dEF=defrost, Pud=pull-down,
Sc=condenser sensor
o02 oFF Sc oFF oFF oFF oFF oFF oFF
Serial address o03 0 247 0 0 0 0 0 -
Password o05 no 999 no no no no no no
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 -
Cooling/heating
rE=refrigeration (cooling)
Ht=heating
o07 rE Ht rE rE rE rE Ht rE
Display resolution
0.1=steps of 0.1 °C
0.5=steps of 0.5 °C,
1.0=steps of 1.0 °C
o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1
Relay 1 counter
(1 count=100 cycles of operation)
o23 0 999 0 0 0 0 0 -
Predefined applications o61 AP0 AP5 AP0 AP1 AP2 AP3 AP4 -
Save settings as factory
WARNING: the earlier factory settings are
overwritten
o67 no yES no no no no no -
Display at defrost
Air=actual air temperature, FrE=freezed
temperature, -d-="-d-" is displayed
o91 Air -d- -d- - -d- -d- - -d-
Note: hidden parameters are greyed out
ENGLISH