| 18 DKRCE.PI.RL0.F6.MLInstruction sheet | ERC 211
Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Polarity P--
DI1 input polarity
nc=normally closed, no=normally open
P73 nc no no no no no no no
Keyboard lock enable P76 no yES no no no no no -
Readouts u--
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time to elapse,
S3=wait for compressor OFF time to elapse-
restart time, S4=drip OFF delay after defrost,
S10=cooling stop,
S11=cooling stopped by thermostat/heating
OFF, S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
u00 S0 S32 --
Air temperature (Sair) u01 -100.0 200.0 C/F ---
Read the present regulation reference u02 -100.0 200.0 C/F ---
DI1 input u10 oFF on ---
Status of night operation u13 oFF on ---
Condenser temperature (Sc) U09 -100.0 200.0 C/F ---
Compressor relay status u58 oFF on ---
Firmware version readout u80 000 999 ---
Note: hidden parameters are greyed out
ENGLISH