EasyManua.ls Logo

Danfoss ERC 213 - Controller Setup and Configuration; 4.5 Power Supply Requirements; 4.6 Sensor Configurations; 4.7 Electrical Noise Prevention

Danfoss ERC 213
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
| 13DKRCE.PI.RL0.G7.ML
Installation Guide | ERC 213
FEATURES DESCRIPTION
Output (continued)
DO2 Defrost relay:
8 A, 2 FLA / 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1
DO3 Fan relay:
3 A, 2 FLA/12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
Display LED display, 3 digits, decimal point and multi-function icons, °C + °F scale
Operating conditions -10 – 55 °C (14 – 131 °F), 90% Rh
Storage conditions -40 – 70 °C (-40 – 158 °F), 90% Rh
Protection
Front: IP65 (Gasket integrated)
Rear: IP00
Environmental Pollution degree II, non-condensing
Overvoltage category
II - 230 V supply version - (ENEC, UL recognized)
III - 115 V supply version - (UL recognized)
Resistance to heat and fire
Category D (UL94-V0)
Temperature for ball pressure test statement According to Annex G”
(EN 60730-1)
EMC category Category I
Approvals
UL recognition (US & Canada) (UL 60730-1)
ENEC (EN 60730-1)
CQC
CE (LVD & EMC Directive)
EAC (GHOST)
NSF
ROHS2.0
HACCP temperature monitoring in compliance with EN134785 Class I,
when used with AKS 12 sensor
ENGLISH

Other manuals for Danfoss ERC 213

Related product manuals