EasyManuals Logo

Danfoss ERC 213 Installation Guide

Danfoss ERC 213
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
| 14 DKRCE.PI.RL0.G7.ML
Installation Guide | ERC 213
ENGLISH
8 - Predefined Application Setup
App Mode Description Temp. Def. type Def. end
App 0 Cooling None (no preset application)
App 1 Cooling
Medium temperature ventilated refrigeration units with timed
natural defrost
(2 – 6 °C) Natural Time
App 2 Cooling
Medium temperature ventilated refrigeration units with timed
electrical defrost
(0 – 4 °C) Electrical Time
App 3 Cooling
Low temperature ventilated refrigeration units with timed
electrical defrost
(-26 – -20 °C) Electrical Time
App 4 Cooling
Medium temperature ventilated refrigeration units with
electrical defrost (by temperature)
(0 – 4 °C) Electrical Temperature
App 5 Cooling
Low temperature ventilated refrigeration units with electrical
defrost (by temperature)
(-26 – -20 °C) Electrical Temperature
App 6 Cooling None (no preset application) with simplified parameter list
SairDI1DI2 SairDI1DI2 SairDI1DI2 S5
APP 1APP 2/3 APP 4/5
DO1
230
V AC
DO2DO3 DO1
230
V AC
DO3DO2 DO1
230
V AC
DO3DO2

Other manuals for Danfoss ERC 213

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 213 and is the answer not in the manual?

Danfoss ERC 213 Specifications

General IconGeneral
Supply Voltage230 V AC
Dimensions75 x 33 x 85 mm
Digital Inputs2
Enclosure RatingIP20
Input Voltage230 V AC
Housing MaterialPlastic
ApplicationRefrigeration
Storage Temperature-20 - 70 °C
Relative Humidity20% to 80% non-condensing
Protection ClassClass II
Weight0.2 kg
Operating Temperature-10°C to +50°C
Power Consumption3 W