14-89 Option Detection
Selects the behavior of the adjustable frequency drive when a
change in the option configuration is detected.
Option: Function:
[0]
*
Protect Option
Config.
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
[1] Enable Option
Change
Changes drive settings and is used
when modifying the system configu-
ration. This parameter setting will
return to [0] after an option change.
14-90 Fault Level
Option: Function:
[0]
*
Off Use this parameter to customize fault levels. Use
[0] "Off" with caution as it will ignore all warnings
and alarms for the chosen source.
[1] Warning
[2] Trip
[3] Trip Lock
Failure Alarm Off Warning Trip Trip Lock
10 V low 1 X X *
24 V low 47 X X*
1.8V supply low 48 X X*
Voltage limit 64 X X*
Ground fault during ramping 14 X* X
Ground fault 2 during cont.
operation
45 X* X
Torque Limit 12 X X*
Table 3.3 Table for selection of choice of action when selected alarm appear:
Parameter Descriptions FC 300 Programming Guide
3-126 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3