RS8KE102 | 19
© Danfoss | ADAP-KOOL® | 2018.11
COL Parameters >
Cool
Function Default Units
Ct1 CL1 Target Cool 1 Target Temperature (10.0-40.0°C) 40.0 °C/°F
Cb1 CL1 PreDelay Cool 1 Pre Delay (0-240) 0 m
Ca1 CL1 PostDelay Cool 1 Post Delay (0-240) 0 m
Ct2 CL2 Target Cool 2 Target Temperature (10.0-40.0°C) 40.0 °C/°F
Cb2 CL2 PreDelay Cool 2 Pre Delay (0-240) 240 m
Ca2 CL2 PostDelay Cool 2 Post Delay (0-240) 240 m
Ct3 CL3 Target Cool 3 Target Temperature (10.0-40.0°C) 40.0 °C/°F
Cb3 CL3 PreDelay Cool 3 Pre Delay (0-240) 240 m
Ca3 CL3 PostDelay Cool 3 Post Delay (0-240) 240 m
Ct4 CL4 Target Cool 4 Target Temperature (10.0-40.0°C) 40.0 °C/°F
Cb4 CL4 PreDelay Cool 4 Pre Delay (0-240) 240 m
Ca4 CL4 PostDelay Cool 4 Post Delay (0-240) 240 m
CLr CL Range +/- Cool Range +/- (0.0-10.0K) 0.5 K/F
CL1 CL Ambient
Lockout
Cool Mode Ambient Lockout (0.0-85.0°C) 15.6 °C/°F
CL2 CL Lockout
Range +/-
Cool Mode Ambient Lockout Range +/-
(0.0-10.0K)
1.1 K/F
CnS CL Night Setback Cool Mode Night Setback (0.0-30.0K) 0.6 K/F
Cs1 CL SupplyAir Cool Mode Supply Air Target for VS Fan
(0.0-100.0°C)
15.0 °C/°F
Cm1 CL Min Fan
Speed
Cool Mode Min Fan Speed (0.0-100.0) 50.0 %
Cm2 CL Max Fan
Speed
Cool Mode Max Fan Speed (0.0-100.0) 75.0 %
CC1 CL Min Compr 1
Speed
Cool Min Compressor 1 Speed (0.0-100.0) 5.0 %
CC2 CL Min Compr 2
Speed
Cool Min Compressor 2 Speed (0.0-100.0) 30.0 %
CC3 CL Min Compr 3
Speed
Cool Min Compressor 3 speed (0.0-100.0) 30.0 %
CC4 CL Min Compr 4
Speed
Cool Min Compressor 4 speed (0.0-100.0) 30.0 %
CLi PI Integ Time 120
CLg PI Gain 8.0
Cns CL Neutral SA 20.0 °C/°F
Rt1 HR1 Target Heat Reclaim 1 Target Temperature (10.0-
40.0°C)
22.2 °C/°F