Data Logging
How it works
Logs the list of points below using the logging interval.). The parameter is located at Parameters-
>General.  Set y37(Logging Interval) to the frequency of logging and  y36(Enable Logging).  to 
Yes to start the logging.
Data Log Points
1.  Zone 1      Zone 1 Sensor
2.  Zone 2      Zone 2 Sensor(if used)
3.  Zone 3      Zone 3 Sensor(if used)
4.  ZoneTemp    Zone Temp used for control
5.  ZoneRH      ZoneRH(may be local or global sensor)
6.  ZoneDewpoint    Calculated Zone Dewpoint
7.  SupplyAir    Supply Air Sensor
8.  ReturnAir     Return Air Sensor
9.  MixedAir     Return Air Sensor
10.  OutdoorAir    Outdoor Air Sensor(may be local or global sensor)
11.  OutdoorRH    Outdoor RH Sensor(may be local or global sensor)
12.  OutdoorDewpoint   Calculated Outdoor Dewpoint
13.  GlobalSchedules    Bit map of the first 16 refrigeration schedules
14.  AlarmStatus    Alarm Status
15. Mode   MCX-RTU Mode
16.  EffSetp      Calculated Setpoint(heat or cool setpoint depending on    
    mode)
17.  FanOut      Fan Control Output
18.  FanFail      Fan Proof not on when FanOut is ON.
19.  PhaseLoss    On means PhaseLoss is good
20.  ShutdownFlag    One of the shutdown DI’s is active
21.  CoolHeatModeGlobal   What is the control mode(0 = Cool, 1 = Heat)
22.  NightSetback    Night Setback is active
23.  SystemOnOff    Master Switch Status
24.  CoolStatus1    Cool 1 Status
25.  CoolStatus2    Cool 2 Status
26.  CoolStatus3    Cool 3 Status
27.  CoolStatus4    Cool 4 Status
28.  AuxHeatStatus1    Aux Heat Status 1
29.  AuxHeatStatus2    Aux Heat Status 2
30.  FanStatusAO    Fan AO Status – 0-100%
31.  DamperStatusAO    Damper AO Status – 0-100%
32.  GlobalOutdoorTemp  Value of Global Outdoor Temp
The Data Log file may be converted to an Excel file by using the DecodeLog converter program.  
The program can be requested from Danfoss Tech Support.