User Guide | MCX-RTU Rooftop
RS8KE102 | 35
© Danfoss | ADAP-KOOL® | 2018.11
DI DIGITAL INPUTS Min Max Type
17 Cool 4 Proof 0 1 N.O.
18 (Located on Expansion Module) 0 1 N.C.
19 (Located on Expansion Module) 0 1 N.C.
20 (Located on Expansion Module) 0 1 N.C.
21 (Located on Expansion Module) 0 1 N.C.
22 (Located on Expansion Module) 0 1 N.C.
23 (Located on Expansion Module) 0 1 N.C.
24 (Located on Expansion Module) 0 1 N.C.
25 (Located on Expansion Module) 0 1 N.C.
26 (Located on Expansion Module) 0 1 N.C.
AO ANALOG OUTPUTS Min Max Type
1 Fan AO 0 % 100 % 0-10 V
2 VS Compr 1 0 % 100 % 1-5 V
3 VS Compr 2 0 % 100 % 1-5 V
4 VS Compr 3 0 % 100 % 1-5 V
5 VS Compr 4 0 % 100 % 1-5 V
6 Damper AO 0 % 100 % 2-10 V
7 Not Available 0 % 100 % NO
8 Not Available 0 % 100 % NO
9 (Located on Expansion Module) 0 % 100 % NO
10 (Located on Expansion Module) 0 % 100 % NO
11 (Located on Expansion Module) 0 % 100 % NO
12 (Located on Expansion Module) 0 % 100 % NO
DO DIGITAL OUTPUTS Min Max Type
1 Cool 1 0 1 N.O.
2 Cool 2 0 1 N.O.
3 Cool 3 0 1 N.O.
4 Cool 4 0 1 N.O.
5 Aux HT 1 0 1 N.O.
6 Aux HT 2 0 1 N.O.
7 Aux HT 3 0 1 N.O.
8 Aux HT 4 0 1 N.O.
9 Reheat 0 1 N.O.
10 Damper 0 1 N.O.
11 HT RCLM 1 0 1 N.O.
12 HT RCLM 2 0 1 N.O.
13 Heat Pump 0 1 N.O.
14 Fan Low 0 1 N.O.
15 Fan High 0 1 N.C.
16 (Located on Expansion Module) 0 1 N.O.
17 (Located on Expansion Module) 0 1 N.O.
18 (Located on Expansion Module) 0 1 N.O.
19 (Located on Expansion Module) 0 1 N.O.
20 (Located on Expansion Module) 0 1 N.O.
21 (Located on Expansion Module) 0 1 N.O.
22 (Located on Expansion Module) 0 1 N.O.
23 (Located on Expansion Module) 0 1 N.O.