Danfoss MCX-RTU - Wiring Diagram - Bottom Side

Danfoss MCX-RTU
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Guide | MCX-RTU Rooftop
RS8KE102 | 7
© Danfoss | ADAP-KOOL® | 2018.11
MCX152V - TOP
MCX152V- BOTTOM
STEPPER
MOTOR 2
RS485-1
SD/MMC
ST2 4
ST2 3
ST2 2
ST2 1
COM 1
D1 +
D1 -
RS485-2
COM 2
D2 +
D2 -
DIGITAL INPUT 18
DIGITAL OUTPUT 9-12 DIGITAL OUTPUT 13-15
STEPPER BACKUP
COM
+ BATT
DIGITAL INPUT 1-8 DIGITAL INPUT 9-16
POWER
SUPPLY
L
N
MEMORY CARD ANALOG OUTPUT 1-6 ANALOG INPUT 1-7
CANCAN-RJ
ETHERNET DIGITAL INPUT 17
ANALOG INPUT 8-14
COM
CANL
CANH
R120
COM 17
DI 17
DIGITAL OUTPUT 6-8
NO 8
C 8
NO 7
C 7
NO 6
C 6
DIGITAL OUTPUT 1-5
NO 3
C 3
NO 2
C 2
NO 5
C 5
NO 4
C 4
NO 1
C 1
CAN-RJ
ETH
STEPPER
MOTOR 1
ST1 4
ST1 3
ST1 2
ST1 1
AO 6
AO 5
AO 4
COM
AO 3
AO 2
AO 1
COM
DI 17H
15V+
COM
DI 9
DI 10
DI 11
DI 12
COM
DI 13
DI 14
DI 15
DI 16
COM
DI 1
DI 2
DI 3
DI 4
COM
DI 5
DI 6
DI 7
DI 8
DI 18H
DI 18
COM 18
C 9
NO 9
C 10
NO 10
C 11
NO 11
C 12
NO 12
C 13
C 13
NO 13
NC 13
C 14
NO 14
NC 14
C 15
NO 15
NC 15
COM
COM
15V+
AI 7
AI 6
AI 5
5V+
AI 4
AI 3
AI 2
AI 1
COM
COM
15V+
AI 14
AI 13
AI 12
5V+
AI 11
AI 10
AI 9
AI 8
Danfoss
80G8043.02
Wiring Diagram MCX 152V - top and bottom
Input Voltage
110-230 V AC
Stepper Backup
NOT USED
Fan Proof
Phase Loss
Shutdown 1
Shutdown 2
Fan Drive Fault
Compr 1 Drive Fault
Compr 2 Drive Fault
Compr 3 Drive Fault
Compr 4 Drive Fault
Filter Clogged Fault
Damper Override
Title 24
Schedule Override
Cool 1 Proof
Cool 2 Proof
Cool 3 Proof
Reheat (N.O.)
Damper (N.O.)
Heat Reclaim 1 (N.O.)
Heat Reclaim 2 (N.O.)
Heat Pump (N.O.)
Fan Low Speed (N.O.)
Fan High Speed (N.C.)
Cool 1 (N.O.)
Cool 2 (N.O.)
Cool 3 (N.O.)
Cool 4 (N.O.)
Aux Heat 1 (N.O.)
Aux Heat 2 (N.O.)
Aux Heat 3 (N.O.)
Aux Heat 4 (N.O.)
Cool 4 Proof
Not Used
Optional -
Remote Display
Optional IO
Expansion