Option 90 - De ne Remote Sensor Type
(Remote sensor 1 - Backplate connection b)
This allows type of remote sensor input type to be
de ned. Press + until Option 90 is displayed, use V or
Λ to select required setting.
0 = No Sensor (Factory setting)
1 = Remote room or Duct sensor, internal sensor
disabled
2 = Remote limit ( oor) sensor, de ne setpoint in
option 93
3 = Digital input for window, card reader, or teleswitch,
de ne functionality in option 94
4 = Outdoor temperature sensor (information only -
no control via sensor reading)
Option 91 - De ne Remote Sensor Type
(Remote sensor 2 - Backplate connection C)
This allows type of remote sensor input type to be
de ned. Press + until Option 91 is displayed, use V or
Λ to select required setting.
0 = No Sensor (Factory setting)
1 = Remote room or Duct sensor, internal sensor
disabled
2 = Remote limit ( oor) sensor, de ne setpoint in
option 93
3 = Digital input for window, card reader, or teleswitch,
de ne functionality in option 94
4 = Outdoor temperature sensor (information only -
no control via sensor reading)