VLT® 5000 Crane
PNU Parameter Range Factory setting Changes Unit Conversion Data Protection
#
7xx
description
Crane functions
during
operation
index index type level
701 Load low 0 - 5000RPM 2500RPM No 11 67 6 1
702 Load high 0 - 1250RPM 1250RPM No 11 67 6 1
703 Load monitoring Enable No 0 0 5 1
704 Low speed at error 5 - 200RPM 50 RPM No 11 67 5 1
705 Brake on RPM 0 - 50RPM 20 RPM No 11 67 5 1
707 Hoist direction Forward No 0 0 5 1
708 Start torque 0 - 170% 100% No 27 0 5 1
709 Ramp torque 0.2-2sec. 0.2sec. No 4 -1 5 1
712 Brake monitoring Enable Yes 0 0 5 1
713 Derating lowering 0.6 - 1 0.8 No 0 -2 5 1
714 Derating hoisting 0.6 - 1 1 No 0 -2 5 1
715 Mech. brake on
delay
0,1 - 20 sec. 0,5 sec. Yes 4 -1 5 1
716 Mech. brake off
delay
0,1 - 20 sec. 0,5 sec. Yes 4 -1 5 1
718 Encoder
monitoring
Enable No 0 0 5 1
720 Drum inertia 1 0 - 1 Depends on unit No 0 -4 6 1
721 Gear ratio 1 0 - 200 Depends on unit No 0 -2 6 1
722 Gear inertia 1 0 - 1 Depends on unit No 0 -4 6 1
723 Mean radius 1 0 - 2 Depends on unit No 0 -3 6 1
724 Drum inertia 2 0 - 1 Depends on unit No 0 -4 6 1
725 Gear ratio 2 0 - 200 Depends on unit No 0 -2 6 1
726 Gear inertia 2 0 - 1 Depends on unit No 0 -4 6 1
727 Mean radius 2 0 - 2 Depends on unit No 0 -3 6 1
740 Power limit function Constant power No 0 0 5 1
741 Mechanical speed
N1
Depends on unit No 11 0 6 1
742 Power at N1 Depends on unit No 9 1 6 1
743 Mechanical speed
at N2
Depends on unit No 11 67 6 1
744 Power at N2 Depends on unit No 9 1 6 1
745 Mechanical speed at
N3
Depends on unit No 11 67 6 1
746 Power at N3 Depends on unit No 9 1 6 1
747 Mechanical speed at
N4
Depends on unit No 11 67 6 1
748 Power at N4 Depends on unit No 9 1 6 1
749 Mechanical speed
N5
Depends on unit No 11 67 6 1
750 Power at N5 Depends on unit No 9 1 6 1
751 Mechanical speed
N6
Depends on unit No 11 67 6 1
752 Power at N6 Depends on unit No 9 1 6 1
753 Mechanical speed
N7
Depends on unit No 11 67 6 1
754 Power at N7 Depends on unit No 9 1 6 1
755 Power Loss N1 Depends on unit No 9 1 6 1
756 Power Loss N2 Depends on unit No 9 1 6 1
757 Power Loss N3 Depends on unit No 9 1 6 1
758 Power Loss N4 Depends on unit No 9 1 6 1
759 Power Loss N5 Depends on unit No 9 1 6 1
760 Power Loss N6 Depends on unit No 9 1 6 1
761 Power Loss N7 Depends on unit No 9 1 6 1
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.N4.02 - VLT is a registered Danfoss trademark
48