VLT
®
5000/6000/8000 Series
Introduction
■
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5300 5350 5450 5500
Normal overload torque (110 %):
Output current I
VLT,N
[A] (380-440 V) 480 600 658 745
I
VLT, MAX
(60 s) [A] (380-440 V) 528 660 724 820
I
VLT,N
[A] (441-500 V) 443 540 590 678
I
VLT, MAX
(60 s) [A] (441-500 V) 487 594 649 746
Output S
VLT,N
[kVA] (380-440 V) 333 416 456 516
S
VLT,N
[kVA] (441-500 V) 384 468 511 587
Typical shaft output (380-440 V) P
VLT,N
[kW] 250 315 355 400
Typical shaft output (380-440 V) P
VLT,N
[HP] 300 350 450 500
Typical shaft output (441-500 V) P
VLT,N
[kW] 315 355 400 500
Typical shaft output (441-500 V) P
VLT,N
[HP] 350 450 500 600
High overload torque (150 %):
Output current I
VLT,N
[A] (380-440 V) 395 480 600 658
I
VLT, MAX
(60 s) [A] (380-440 V) 593 720 900 987
I
VLT,N
[A] (441-500 V) 361 443 540 590
I
VLT, MAX
(60 s) [A] (441-500 V) 542 665 810 885
Output S
VLT,N
[kVA] (380-440 V) 274 333 416 456
S
VLT,N
[kVA] (441-500 V) 313 384 468 511
Typical shaft output (380-440 V) P
VLT,N
[kW] 200 250 315 355
Typical shaft output (380-440 V) P
VLT,N
[HP] 300 350 450 500
Typical shaft output (441-500 V) P
VLT,N
[kW] 250 315 355 400
Typical shaft output (441-500 V) P
VLT,N
[HP] 350 450 500 600
Max. cross-section of copper cable to motor, brake 2x150 2x185 2x240 2x300
and loadsharing (380-440 V) [mm
2
]
5)
3x70 3x95 3x120 3x150
Max. cross-section of copper cable to motor, brake 2x120 2x150 2x185 2x300
and loadsharing (441-500 V) [mm
2
]
5)
3x70 3x95 3x95 3x120
Max. cross-section of aluminium cable to motor, brake 2x185 2x240 2x300
and loadsharing (380-440 V) [mm
2
]
5)
3x120 3x150 3x185 3x185
Max. cross-section of aluminium cable to motor, brake 2x150 2x185 2x240
and loadsharing (441-500) [mm
2
]
5)
3x95 3x120 3x150 3x185
Max. cross-section of copper cable to motor, brake 2x250mcm 2x350mcm 2x400mcm 2x500mcm
and loadsharing (380-440 V) AWG]
2) 5)
3x2/0 3x3/0 3x4/0 3x250mcm
Max. cross-section of copper cable to motor, brake 2x4/0 2x300mcm 2x350mcm 2x500mxm
and loadsharing (441-500 V) AWG]
2) 5)
31/0 3x3/0 3x3/0 3x4/0
Max. cross-section of aluminium cable to motor, brake 2x350mcm 2x500mcm 2x600mcm 2x700mcm
and loadsharing (380-440 V) AWG]
2) 5)
3x4/0 3x250mcm 3x300mcm 3x350mcm
Max. cross-section of aluminium cable to motor, brake 2x300mcm 2x400mcm 2x500mcm 2x600mcm
and loadsharing (441-500 V) AWG]
2) 5)
3x3/0 3x4/0 3x250mcm 3x300mcm
1. For type of
fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable
cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always
comply with national and local regulations on min. cable cross-section.
5. Connection stud 2 x M12/3 x M12.
MG.56.A2.02 - VLT is a registered Danfoss trademark
7