10-22 COS Filter 3
Range: Function:
0* [0 -
65535 ]
Enter the value for COS lter 3, to set up the
lter mask for PCD 3. When operating in COS
(change-of-state), this function lters out bits in
PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range: Function:
0* [0 -
65535 ]
Enter the value for COS lter 4 to set up the
lter mask for PCD 4. When operating in COS
(change-of-state), this function lters out bits in
PCD 4 that should not be sent if they change.
3.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters
and dening programming set-up.
10-31 Store Data Values
Option: Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values are
retained at power-down.
[0] * O Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values from the active set-
up in the non-volatile memory. The selection
returns to [0] O when all values have been
stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to [0]
O when all parameter values have been stored.
10-33 Store Always
Option: Function:
[0] * O Deactivates non-volatile storage of data.
[1] On Stores parameter data received via DeviceNet in
EEPROM non-volatile memory as default.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
104 Danfoss A/S © 03/2015 All rights reserved. MG11CE02