3.15 Parameters: 15-** Main Menu - Drive
Information
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.15.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned o.
15-01 Running Hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the motor has run.
Reset the counter in
parameter 15-07 Reset Running Hours
Counter. The value is saved when the
frequency converter is turned
o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 -
2147483647
kWh]
Registers the power consumption of
the motor as a mean value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
temperature faults, which have occurred.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
overvoltages, which have occurred.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset
NOTICE
The reset is carried out by pressing
[OK].
No reset of the kWh counter is desired.
15-06 Reset kWh Counter
Option: Function:
[1] Reset counter Press [OK] to reset the kWh counter to zero
(see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not
reset
No reset of the running hours counter is
desired.
[1] Reset
counter
Select [1] Reset counter and press [OK] to reset
the running hours counter
(parameter 15-01 Running Hours) and
parameter 15-08 Number of Starts to zero (see
also parameter 15-01 Running Hours).
15-08 Number of Starts
Range: Function:
0* [0 - 2147483647 ] This is a readout parameter only. The
counter shows the number of starts and
stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to
be logged.
[0] * None
[1397] Alert Alarm Word
[1398] Alert Warning Word
[1399] Alert Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
Parameter Descriptions
VLT
®
HVAC Drive FC 102
124 Danfoss A/S © 03/2015 All rights reserved. MG11CE02
33