Term.
no.
96 97 98 99
U V W
PE
1
)
Motor voltage 0-100% of mains
voltage.
3 wires out of motor
U1 V1 W1
PE
1
)
Delta-connected
W
2
U2 V2 6 wires out of motor
U1 V1 W1
PE
1
)
Star-connected U2, V2, W2
U2, V2 and W2 to be intercon-
nected separately.
Table 3.14
1)
Protected Earth Connection
NOTICE
In motors without phase insulation paper or other
insulation reinforcement suitable for operation with
voltage supply (such as a frequency converter), fit a Sine-
wave filter on the output of the frequency converter.
U
1
V
1
W
1
175ZA114.11
96 97 98
96 97 98
FC
FC
Motor
Motor
U
2
V
2
W
2
U
1
V
1
W
1
U
2
V
2
W
2
Illustration 3.49 Star/Delta Connections
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
44 MG33U402 - Rev. 2013-12-16