Loading...
Enclosure Power [kW] Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A3 1.1-7.5 gG-6 (3)
gG-10 (2)
gG-16 (2)
gG-25
B2 22-30 gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 - -
C2 75-90 gG-63 (30)
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-80 (30)
gG-100 (37)
gG-125 (45)
gG-160 (55-75)
- -
C3 44-55
gG-80
gG-100
gG-100
gG-125
D -
gG-125 (37)
gG-160 (45)
gG-200 (55-75)
aR-250 (90)
aR-315 (110)
aR-350 (132-160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
gG-125 (37)
gG-160 (45)
gG-200 (55-75)
aR-250 (90)
aR-315 (110)
aR-350 (132-160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
- -
E -
aR-700 (355-400)
aR-900 (500-560)
aR-700 (355-400)
aR-900 (500-560)
- -
F -
aR-1600 (630-900)
aR-2000 (1000)
aR-2500 (1200)
aR-1600 (630-900)
aR-2000 (1000)
aR-2500 (1200)
- -
Table 3.29 525-690 V, Frame Sizes A, B, C, D, E and F
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16 61