Surroundings
Enclosure enclosure type A IP20, IP55
Enclosure enclosure type A, B IP21, IP55
Enclosure kit available enclosure type A IP21/TYPE 1/IP 4X top
Vibration test 1.0 g
Max. relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated class 3C2
Aggressive environment (IEC 721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature Max. 122 °F/50 °C
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation 32 °F/0 °C
Minimum ambient temperature at reduced performance 14 °F/-10 °C
Temperature during storage/transport -13 to 149 °F/-25 to +65/70 °C
Maximum altitude above sea level without derating 3280 ft/1000 m
Maximum altitude above sea level with derating 9842 ft/3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
General Specications Operating Instructions
MG34M422 Danfoss A/S © Rev. 2013-07-03 All rights reserved. 167
8 8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 302 and is the answer not in the manual?

Danfoss VLT CDS 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 302
CategoryDC Drives
LanguageEnglish

Related product manuals