The Start-up Wizard for compressor functions
28-13 Boost Duration
60 s
5
6
28-01 Interval between Starts
130BD874.11
28-11 Low Speed Running Time
20 min
28-02 Minimum Run Time
3
28-00 Short Cycle Protection
[1]
Enabled
1
28-10 Oil Return Management
[1]
On
4
2
300 s
60 s
Illustration 1.16 Compressor Function Wizard
Compressor function wizard
Parameter Option Default Function
28-00 Short Cycle Protection
[0] Disabled
[1] Enabled
[1] Enabled Select if short cycle protection is to be used.
28-01 Interval between Starts
0-3600 s 300 s Enter the minimum allowed time between
starts.
28-02 Minimum Run Time
10-3600 s 60 s Enter the minimum allowed time to run
before stop.
28-10 Oil Return Management
[0] Off
[1] On
[1] On Select if Oil Return Management is to be used.
28-11 Low Speed Running Time
1-1400 min 20 min Enter the low speed running time.
28-13 Boost Duration
10-3600 s 60 s Enter the boost duration for the oil return.
Table 1.14 Compressor Function
Quick Guide Quick Guide
16 Danfoss A/S © Rev. 09/2014 All rights reserved. MG18M102
1
1

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals