Closed loop quick guide
Parameter Option Default Function
Parameter 0-01 Language [0] English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
[28] Bras.port
0 Select the language for the display.
Parameter 0-06 GridType [0] 200–240 V/50 Hz/IT-grid
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT-grid
[11] 380–440 V/50 Hz/Delta
[12] 380–440 V/50 Hz
[20] 440–480 V/50 Hz/IT-grid
[21] 440–480 V/50 Hz/Delta
[22] 440–480 V/50 Hz
[30] 525–600 V/50 Hz/IT-grid
[31] 525–600 V/50 Hz/Delta
[32] 525–600 V/50 Hz
[100] 200–240 V/60 Hz/IT-grid
[101] 200–240 V/60 Hz/Delta
[102] 200–240 V/60 Hz
[110] 380–440 V/60 Hz/IT-grid
[111] 380–440 V/60 Hz/Delta
[112] 380–440 V/60 Hz
[120] 440–480 V/60 Hz/IT-grid
[121] 440–480 V/60 Hz/Delta
[122] 440–480 V/60 Hz
[130] 525–600 V/60 Hz/IT-grid
[131] 525–600 V/60 Hz/Delta
[132] 525–600 V/60 Hz
Size related Select the operating mode for restart after
reconnection of the frequency converter to
mains voltage after power-down.
Parameter 0-60 Main Menu Password 0–999 0 Dene the password for access to the LCP.
Parameter 1-00 Conguration Mode [0] Open loop
[3] Closed loop
[0] Open loop Select closed loop.
Parameter 1-13 Compressor Selection [24] VZH028-R410A
[25] VZH035-R410A
[26] VZH044-R410A
[27] VLZ028
[28] VLZ035
[29] VLZ044
Size related Select the used compressor.
Parameter 3-02 Minimum Reference 0–200 Hz 30 Hz The minimum reference is the lowest value
obtainable by summing all references.
Parameter 3-03 Maximum Reference 0–200 Hz 200 Hz The maximum reference is the highest
obtainable by summing all references.
Parameter 3-10 Preset Reference -100 100 % 0% Set up a x setpoint in preset reference [0].
Parameter 3-15 Reference 1 Source [0] No function
[1] Analog in 53
[2] Analog in 54
[7] Pulse input 29
[11] Local bus reference
[1] Analog in 53 Select the input to be used for the reference
signal.
Parameter 3-41 Ramp 1 Ramp Up
Time
0.05–3600.0 s 90.00 s Ramp-up time from 0 to parameter 1-25 Motor
Nominal Speed.
How to Program
VLT
®
Compressor Drive CDS 803
14 Danfoss A/S © 06/2019 All rights reserved. MG18P202
22

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals