7.7.1 Removing the Heatsink Access Panel
The adjustable frequency drive has an optional access
panel for accessing the heatsink.
Figure 7.30 Heatsink Access Panel
1. Do not run the adjustable frequency drive during
heatsink access panel removal.
2. If the adjustable frequency drive is mounted on a
wall, or the back of it is otherwise inaccessible,
reposition it so that the back is fully accessible.
3. Remove the screws (0.1 [3 mm] internal hex)
connecting the access panel to the back of the
enclosure. There are five or nine screws
depending on the size of the adjustable
frequency drive.
Reinstall in reverse order of this procedure and tighten
fasteners according to chapter 1.7 General Torque
Tightening Values.
Disassembly and Assembly In...
Service Manual
MG94A222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 119