5 General Specifications
Mains supply (L1-1, L2-1, L3-1, L1-2, L2-2, L3-2)
Supply voltage FC 302: 380-500 V ±10%
Supply voltage FC 302: 525-690 V ±10%
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage. Power-up and full
torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage.
Supply frequency 50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0% of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1-1, L2-1, L3-1, L1-2, L2-2, L3-2 (power-ups) maximum 1 time/2 min.
Environment according to EN60664-1 over-voltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 500/600/690V
maximum.
Motor output (U, V, W)
Output voltage 0 - 100% of supply voltage
Output frequency 0 - 800* Hz
Switching on output Unlimited
Ramp times 0.01 - 3600 s
* Voltage and power dependent
Torque characteristics
Starting torque (Constant torque) maximum 160% for 60 s
1)
Starting torque maximum 180% up to 0.5 s
1)
Overload torque (Constant torque) maximum 160% for 60 s
1)
Starting torque (Variable torque) maximum 110% for 60 s
1)
Overload torque (Variable torque) maximum 110% for 60 s
Torque rise time in (independent of fsw) 10 ms
Torque rise time in FLUX (for 5 kHz fsw) 1 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Digital inputs
Programmable digital inputs 4 (6)
Terminal number 18, 19, 27
1)
, 29, 32, 33,
Logic PNP or NPN
Voltage level 0 - 24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 0 - 110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
approx.4
General Specifications
VLT
®
Automation Drive FC 300 12-Pulse
Operating Instructions High Power
94 MG34Q202 - VLT
®
is a registered Danfoss trademark
55

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals