Danfoss VLT FC 101 - Page 10

Danfoss VLT FC 101
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
a
b
B
C
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Enclosure Power [kW (hp)] Height [mm (in)] Width [mm (in)]
Depth
[mm (in)]
Mounting hole [mm (in)]
Maximum
weight
Size IP class 3x200–240 V 3x380–480 V 3x525–600 V A
A
1)
a B b C d e f kg (lb)
I2 IP54 0.75–4.0 (1–5)
332
(13.1)
318.5 (12.53) 115 (4.5) 74 (2.9) 225 (8.9) 11 (0.43) 5.5 (0.22) 9 (0.35) 5.3 (11.7)
I3 IP54 5.5–7.5 (7.5–10)
368
(14.5)
354 (13.9) 135 (5.3) 89 (3.5) 237 (9.3) 12 (0.47) 6.5 (0.26) 9.5 (0.37) 7.2 (15.9)
I4 IP54 11–18.5 (15–25)
476
(18.7)
460 (18.1) 180 (7) 133 (5.2) 290 (11.4) 12 (0.47) 6.5 (0.26) 9.5 (0.37)
13.8
(30.42)
I6 IP54 22–37 (30–50)
650
(25.6)
624 (24.6) 242 (9.5) 210 (8.3) 260 (10.2) 19 (0.75) 9 (0.35) 9 (0.35) 27 (59.5)
I7 IP54 45–55 (60–70)
680
(26.8)
648 (25.5) 308 (12.1) 272 (10.7) 310 (12.2) 19 (0.75) 9 (0.35) 9.8 (0.39) 45 (99.2)
I8 IP54 75–90 (100–125) 770 (30) 739 (29.1) 370 (14.6) 334 (13.2) 335 (13.2) 19 (0.75) 9 (0.35) 9.8 (0.39) 65 (143.3)
1) Including decoupling plate
The dimensions are only for the physical units.
NOTICE
When installing in an application, allow space above and below the units for cooling. The amount of space for free air passage is listed in Table 3.1.
Table 3.3 Dimensions, Enclosure Sizes I2–I8
Installation
VLT
®
HVAC Basic Drive FC 101
8 Danfoss A/S © 05/2016 All rights reserved. MG18A802
33