3.1.2 Frequency Converter Dimensions
A
a
b
B
C
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Enclosure Power [kW (hp)] Height [mm (in)] Width [mm (in)]
Depth
[mm (in)]
Mounting hole [mm (in)]
Maximum
weight
Size IP class 3x200–240 V 3x380–480 V 3x525–600 V A
A
1)
a B b C d e f kg (lb)
H1 IP20
0.25–1.5
(0.33–2)
0.37–1.5
(0.5–2)
195 (7.7) 273 (10.7) 183 (7.2) 75 (3.0) 56 (2.2) 168 (6.6) 9 (0.35)
4.5
(0.18)
5.3 (0.21) 2.1 (4.6)
H2 IP20 2.2 (3)
2.2–4.0
(3–5)
227 (8.9) 303 (11.9) 212 (8.3) 90 (3.5) 65 (2.6) 190 (7.5) 11 (0.43)
5.5
(0.22)
7.4 (0.29) 3.4 (7.5)
H3 IP20 3.7 (5)
5.5–7.5
(7.5–10)
255
(10.0)
329 (13.0) 240 (9.4) 100 (3.9) 74 (2.9) 206 (8.1) 11 (0.43)
5.5
(0.22)
8.1 (0.32) 4.5 (9.9)
H4 IP20
5.5–7.5
(7.5–10)
11–15
(15–20)
296
(11.7)
359 (14.1) 275 (10.8) 135 (5.3) 105 (4.1) 241 (9.5)
12.6
(0.50)
7 (0.28) 8.4 (0.33) 7.9 (17.4)
H5 IP20 11 (15)
18.5–22
(25–30)
334
(13.1)
402 (15.8) 314 (12.4) 150 (5.9) 120 (4.7) 255 (10)
12.6
(0.50)
7 (0.28) 8.5 (0.33) 9.5 (20.9)
H6 IP20
15–18.5
(20–25)
30–45
(40–60)
18.5–30
(25–40)
518
(20.4)
595 (23.4)/635
(25), 45 kW
495 (19.5) 239 (9.4) 200 (7.9) 242 (9.5)
8.5
(0.33)
15 (0.6) 24.5 (54)
H7 IP20
22–30
(30–40)
55–75
(70–100)
37–55
(50–70)
550
(21.7)
630 (24.8)/690
(27.2), 75 kW
521 (20.5) 313 (12.3) 270 (10.6) 335 (13.2)
8.5
(0.33)
17 (0.67) 36 (79)
H8 IP20
37–45
(50–60)
90 (125)
75–90
(100–125)
660 (26) 800 (31.5) 631 (24.8) 375 (14.8) 330 (13) 335 (13.2)
8.5
(0.33)
17 (0.67) 51 (112)
H9 IP20
2.2–7.5
(3–10)
269
(10.6)
374 (14.7) 257 (10.1) 130 (5.1) 110 (4.3) 205 (8) 11 (0.43)
5.5
(0.22)
9 (0.35) 6.6 (14.6)
H10 IP20
11–15
(15–20)
399
(15.7)
419 (16.5) 380 (15) 165 (6.5) 140 (5.5) 248 (9.8) 12 (0.47)
6.8
(0.27)
7.5 (0.30) 12 (26.5)
1) Including decoupling plate
The dimensions are only for the physical units.
NOTICE
When installing in an application, allow space above and below the units for cooling. The amount of space for free air passage is listed in Table 3.1.
Table 3.2 Dimensions, Enclosure Sizes H1–H10
Installation Quick Guide
MG18A802 Danfoss A/S © 05/2016 All rights reserved. 7