3.13.2 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option: Function:
[0] * Off Disables the Smart Logic Controller.
[1] On Enables the Smart Logic Controller.
13-01 Start Event
Option: Function:
Select the Boolean (TRUE or FALSE) input to activate Smart Logic Control.
[0] * FALSE Enters the fixed value of FALSE in the logic rule.
[1] TRUE Enters the fixed value TRUE in the logic rule.
[2] Running See parameter group 5-3* for further description.
[3] In range See parameter group 5-3* for further description.
[4] On reference See parameter group 5-3* for further description.
[5] Torque limit See parameter group 5-3* for further description.
[6] Current limit See parameter group 5-3* for further description.
[7] Out of current range See parameter group 5-3* for further description.
[8] Below I low See parameter group 5-3* for further description.
[9] Above I high See parameter group 5-3* for further description.
[10] Out of speed range
[11] Below speed low See parameter group 5-3* for further description.
[12] Above speed high See parameter group 5-3* for further description.
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning See parameter group 5-3* for further description.
[17] Mains out of range See parameter group 5-3* for further description.
[18] Reverse See parameter group 5-3* for further description.
[19] Warning See parameter group 5-3* for further description.
[20] Alarm (trip) See parameter group 5-3* for further description.
[21] Alarm (trip lock) See parameter group 5-3* for further description.
[22] Comparator 0 Use the result of comparator 0 in the logic rule.
[23] Comparator 1 Use the result of comparator 1 in the logic rule.
[24] Comparator 2 Use the result of comparator 2 in the logic rule.
[25] Comparator 3 Use the result of comparator 3 in the logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the logic rule.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-119
3