16-95 Ext. Status Word 2
Range: Function:
0 N/A* [0 - 4294967295 N/A] Returns the extended warning word 2 sent via the serial communication port in hex code.
16-96 Maintenance Word
Range: Function:
0 N/A* [0 - 4294967295 N/A] Readout of the Preventive Maintenance Word. The bits reflect the status for the programmed pre-
ventive maintenance events in parameter group 23-1*. 13 bits represent combinations of all the
possible items:
Bit 0: Motor bearings
Bit 1: Pump bearings
•Bit 2: Fan bearings
Bit 3: Valve
Bit 4: Pressure transmitter
Bit 5: Flow transmitter
Bit 6: Temperature transmitter
Bit 7: Pump seals
Bit 8: Fan belt
•Bit 9: Filter
Bit 10: Drive cooling fan
Bit 11: Drive system health check
Bit 12: Warranty
Bit 13: Maintenance Text 0
Bit 14: Maintenance Text 1
Bit 15: Maintenance Text 2
Bit 16: Maintenance Text 3
Bit 17: Maintenance Text 4
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-160
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage