21-12 Ext. 1 Maximum Reference
Range: Function:
100.000 Ex-
tPID1Unit*
[par. 21-11 - 999999.999 Ex-
tPID1Unit]
Select the maximum for the Closed-loop 1 Controller.
The dynamics of the PID controller will depend on the value set in this parameter. Please see also
par.21-21
Ext. 1 Proportional Gain
.
NOTE!
Always set the desired value for par.21-12
Ext. 1 Maximum Reference
before setting the values for the PID controller in par. 20-9*.
21-13 Ext. 1 Reference Source
Option: Function:
This parameter defines which input on the adjustable frequency drive should be treated as the
source of the reference signal for the closed-loop 1 controller. Analog input X30/11 and Analog input
X30/12 refer to inputs on the General Purpose I/O.
[0] * No function
[1] Analog input 53
[2] Analog input 54
[7] Pulse input 29
[8] Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[30] Ext. Closed-loop 1
[31] Ext. Closed-loop 2
[32] Ext. Closed-loop 3
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-186
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals