EasyManuals Logo

Danfoss VLT HVAC Series User Manual

Danfoss VLT HVAC Series
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #260 background imageLoading...
Page #260 background image
3.23.2 25-0* System Settings
Parameters related to control principles and configuration of the system.
25-00 Cascade Controller
Option: Function:
For operation of multiple devices (pump/fan) systems where capacity is adapted to actual load by
means of speed control combined with on/off control of the devices. For simplicity, only pump sys-
tems are described.
[0] * Disabled The cascade controller is not active. All built-in relays assigned to pump motors in the cascade
function will be de-energized. If a variable speed pump is connected to the adjustable frequency
drive directly (not controlled by a built-in relay); this pump/fan will be controlled as a single pump
system.
[1] Enabled
25-02 Motor Start
Option: Function:
Motors are directly connected to the line power with a contactor or a soft starter. When the value
of par.25-02
Motor Start
is set to an option other than
Direct on Line
[0], then par.25-50
Lead Pump
Alternation
is automatically set to the default of
Direct on Line
[0].
[0] * Direct on Line Each fixed speed pump is directly connected to line via a contactor.
[1] Soft Starter Each fixed speed pump is connected to line via a soft starter.
[2] Star-Delta
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-236
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals