25-24 SBW De-staging Delay
Range: Function:
15 s* [0 - 3000 s] Immediate de-staging of a fixed speed pump is not desirable during a momentary pressure increase
in the system that exceeds the staging bandwidth (SBW). De-staging is delayed by the length of
time programmed. If the pressure decreases to within the SBW before the timer has elapsed, the
timer is reset.
25-25 OBW Time
Range: Function:
10 s* [0 - 300 s] Staging a fixed speed pump creates a momentary pressure peak in the system, which might exceed
the override bandwidth (OBW). It is not desirable to de-stage a pump in response to a staging
pressure peak. The OBW time can be programmed to prevent staging until the system pressure has
stabilized and normal control has been established. Set the timer to a value that allows the system
to stabilize after staging. The 10-second factory setting is appropriate in most applications. In highly
dynamic systems, a shorter time may be desirable.
25-26 Destage At No-Flow
Option: Function:
The de-stage at the no-flow parameter ensures that when a no-flow situation occurs, the fixed speed
pumps will be de-staged one-by-one until the no-flow signal disappears. This requires that no-flow
detection is active. See par. 22-2*.
If De-stage at No-Flow is disabled the Cascade Controller does not change the normal behavior of
the system.
[0] * Disabled
[1] Enabled
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-240
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals