25-27 Stage Function
Option: Function:
If the stage function is set to
Disabled
[0], par.25-28
Stage Function Time
will not be activated.
[0] Disabled
[1] * Enabled
25-28 Stage Function Time
Range: Function:
15 s* [0 - 300 s] Stage function time is programmed to avoid frequent staging of the fixed speed pumps. The stage
function time starts if it is
Enabled
[1] by par.25-27
Stage Function
, and when the variable speed
pump is running at
Motor Speed High Limit
, par.4-13
Motor Speed High Limit [RPM]
or par.
4-14
Motor Speed High Limit [Hz]
, with at least one fixed speed pump in the stop position. When
the programmed value of the timer expires, a fixed speed pump is staged.
25-29 Destage Function
Option: Function:
The de-stage function ensures that the lowest number of pumps are running to save energy and to
avoid dead head water circulation in the variable speed pump. If the de-stage function is set to
Disabled
[0], the par.25-30
Destage Function Time
will not be activated.
[0] Disabled
[1] * Enabled
25-30 Destage Function Time
Range: Function:
15 s* [0 - 300 s] The de-stage function timer is programmable to avoid frequent staging/de-staging of the fixed
speed pumps. The de-stage function time starts when the adjustable speed pump is running at par.
4-11
Motor Speed Low Limit [RPM]
or par.4-12
Motor Speed Low Limit [Hz]
, with one or more fixed
speed pumps in operation and system requirements satisfied. In this situation, the adjustable speed
pump contributes a little to the system. When the programmed value of the timer expires, a stage
is removed, avoiding dead head water circulation in the adjustable speed pump.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-241
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals