WARNING 62
Output Frequency at Maximum Limit:
The output frequency is higher than the value
set in par. 4-19
WARNING 64
Voltage Limit:
The load and speed combination demands a
motor voltage higher than the actual DC link
voltage.
WARNING/ALARM/TRIP 65
Control Card Over Temperature:
Control card over temperature: The cut-out
temperature of the control card is 80° C.
WARNING 66
Heatsink Temperature Low:
The heat sink temperature is measured as 0°
C. This could indicate that the temperature
sensor is defective and thus the fan speed is
increased to the maximum in case the power
part or control card is very hot.
ALARM 67
Option Configuration has Changed:
One or more options has either been added or
removed since the last power-down.
ALARM 68
Safe Stop Activated:
Safe Stop has been activated. To resume nor-
mal operation, apply 24 V DC to terminal 37,
then send a reset signal (via Bus, Digital I/O,
or by pressing [RESET]). For correct and safe
use of the Safe Stop function follow the rela-
ted information and instructions in the Design
Guide
ALARM 70
Illegal Frequency Configuration:
Actual combination of control board and pow-
er board is illegal.
ALARM 80
Initialization to Default Value:
Parameter settings are initialised to default
setting after a manual (three-finger) reset.
7. Troubleshooting VLT
®
HVAC Drive Operating Instructions
128
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark
7

Other manuals for Danfoss VLT HVAC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC and is the answer not in the manual?

Danfoss VLT HVAC Specifications

General IconGeneral
Enclosure RatingIP20, IP21, IP54, IP55, IP66
Storage Temperature Range-25°C to +70°C
Output Voltage Range0-100% of supply voltage
Communication ProtocolsModbus RTU, BACnet, Ethernet/IP, Profibus DP
Ambient Temperature Range-10°C to +50°C (without derating)
Relative Humidity5% to 95% non-condensing
AltitudeUp to 1000 m without derating
Cooling MethodAir cooled
ApplicationHVAC systems, Pumps, Fans, Compressors
Voltage Range200-240 V, 380-500 V, 525-600 V
Frequency Range0 Hz to 590 Hz

Related product manuals