5.1.9. Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1. Select par. 14-22
2. Press [OK]
3. Select “Initialisation” ( for NLCP se-
lect “2” )
4. Press [OK]
5. Remove power to unit and wait for
display to turn off.
6. Reconnect power and the frequency
converter is reset. Note that first
start-up takes a few more seconds.
NB!
Parameters selected in
Personal
Menu
, will stay present, with de-
fault factory setting.
Par. 14-22 initialises all except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05 Operating data
15-20 to 15-22 Historic log
15-30 to 15-32 Fault log
Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings
(par. 14-50) and fault log settings are reset.
Removes parameters selected in
Personal Menu
.
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power up for Graphical
LCP (GLCP).
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This parameter initialises all except:
15-00
Operating Hours
15-03
Power-up's
15-04
Over temp's
15-05
Over volt's
VLT
®
HVAC Drive Operating Instructions 5. How to operate the frequency converter
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark
53