NB!
When you carry out manual initialisation, you also reset serial communication, RFI
filter settings (par. 14-50) and fault log settings.
Removes parameters selected in
Personal Menu
.
NB!
After initialization and power cycling, the display will not show any information until
after a couple of minutes.
4-56 Warning Feedback Low
Value:
-999999.999 to
+999999.999
-999999.999
Function:
Enter the lower feedback limit. When the
feedback falls below this limit, the display
reads Feedb Low. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01 or
02.
VLT
®
HVAC Drive Operating Instructions 6. How to programme the frequency converter
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark