Par. No. # Parameter description Default value 4-set-up Change during
operation
Conver-
sion index
Type
6-5* Analog Output 42
6-50 Terminal 42 Output [100] Output frequency All set-ups TRUE - Uint8
6-51 Terminal 42 Output Min Scale 0.00 % All set-ups TRUE -2 Int16
6-52 Terminal 42 Output Max Scale 100.00 % All set-ups TRUE -2 Int16
6-53 Terminal 42 Output Bus Control 0.00 % All set-ups TRUE -2 N2
6-54
Terminal 42 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6-6* Analog Output X30/8
6-60 Terminal X30/8 Output [0] No operation All set-ups TRUE - Uint8
6-61 Terminal X30/8 Min. Scale 0.00 % All set-ups TRUE -2 Int16
6-62 Terminal X30/8 Max. Scale 100.00 % All set-ups TRUE -2 Int16
6-63 Terminal X30/8 Output Bus Control 0.00 % All set-ups TRUE -2 N2
6-64 Terminal X30/8 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6. How to programme the frequency converter VLT
®
HVAC Drive Operating Instructions
98