1.7 Specifications
1.7.1 Line Power Supply 1 x 200–240V AC
Normal overload 150% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
PK18
0.18
PK37
0.37
PK75
0.75
P1K5
1.5
P2K2
2.2
Typical Shaft Output [HP] 0.25 0.5 1 2 3
IP 20 Frame M1 Frame M1 Frame M1 Frame M2 Frame M3
Output current
Continuous (3 x 200–240V) [A] 1.2 2.2 4.2 6.8 9.6
Intermittent (3 x 200–240V) [A] 1.8 3.3 6.3 10.2 14.4
Max. cable size:
(line power, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (1 x 200–240V) [A] 3.3 6.1 11.6 18.7 26.4
Intermittent (1 x 200–240V) [A] 4.5 8.3 15.6 26.4 37.0
Max. electrical fuses [A] See section Fuses.
Environment
Estimated power loss [W], Best case/
Typical
1)
12.5/
15.5
20.0/
25.0
36.5/
44.0
61.0/
67.0
81.0/
85.1
Weight enclosure IP20 (lbs [kg]) 2.43 [1.1] 2.43 [1.1] 2.43 [1.1] 3.53 [1.6] 6.61 [3.0]
Efficiency [%], Best case/Typical
1)
95.6/
94.5
96.5/
95.6
96.6/
96.0
97.0/
96.7
96.9/
97.1
Table 1.13 Line Power Supply 1 x 200–240V AC
1. At rated load conditions.
1.7.2
Line Power Supply 3 x 200–240V AC
Normal overload 150% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
PK25
0.25
PK37
0.37
PK75
0.75
P1K5
1.5
P2K2
2.2
P3K7
3.7
Typical Shaft Output [HP] 0.33 0.5 1 2 3 5
IP 20 Frame M1 Frame M1 Frame M1 Frame M2 Frame M3 Frame M3
Output current
Continuous (3 x 200–-240V) [A] 1.5 2.2 4.2 6.8 9.6 15.2
Intermittent (3 x 200–240V) [A] 2.3 3.3 6.3 10.2 14.4 22.8
Max. cable size:
(line power, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (3 x 200–-240V) [A] 2.4 3.5 6.7 10.9 15.4 24.3
Intermittent (3 x 200–240V) [A] 3.2 4.6 8.3 14.4 23.4 35.3
Max. electrical fuses [A] See section Fuses.
Environment
Estimated power loss [W], Best case/
Typical
1)
14.0/
20.0
19.0/
24.0
31.5/
39.5
51.0/
57.0
72.0/
77.1
115.0/
122.8
Weight enclosure IP20 (lbs [kg]) 2.43 [1.1] 2.43 [1.1] 2.43 [1.1] 3.53 [1.6] 6.61 [3.0] 6.61 [3.0]
Efficiency [%], Best case/Typical
1)
96.4/
94.9
96.7/
95.8
97.1/
96.3
97.4/
97.2
97.2/
97.4
97.3/
97.4
Table 1.14 Line Power Supply 3 x 200–240V AC
1. At rated load conditions.