NOTE!
All inputs, outputs, circuits, DC supplies and relay contacts
are galvanically isolated from the supply voltage (PELV)
and other high-voltage terminals.
Surroundings:
Enclosure IP 20
Enclosure kit available. IP 21, TYPE 1
Vibration test 1.0 g
Max. relative humidity 5%-95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature Max. 104°F [40°C]
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation 32°F [0°C]
Minimum ambient temperature at reduced performance 14°F [-10°C]
Temperature during storage/transport -13°–+149°/158°F [-25°–+65°/70°C]
Maximum altitude above sea level without derating 3280 ft [1000 m]
Maximum altitude above sea level with derating 9842 ft [3000 m]
Derating for high altitude, see section on special conditions
Safety standards EN/IEC 61800-5-1, UL 508C
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions
Quick Guide
VLT
®
Micro Drive Quick Guide
MG02B722 - VLT
®
is a registered Danfoss trademark 1-21
1 1