Preventive maintenance, cont.
Checklist (User)
- page 3
Acceptance: The filter is mounted. The
exhaust grille or exhaust plate
(S-mod-
ule) is mounted and fixed with 4 screws.
The grid within the exhaust air wholes on
the CDT 30S and CDT 40S are complete
and fixed.
Acceptance: The dehumidifier stops op-
eration after 10 sec.
-
acceptance: The dehumidifier do not
stop and continues operation.
Acceptance: Free passage through drain
outlet.
Acceptance: The pump starts and emp-
ties container.
Acceptance for starting: The dehumidifier
starts up after 2 sec.
Acceptance for switching off: The dehu-
midifier switches off after 2 sec.
Fill up with water and check that water is
not escaping the container.
Water container is removed
during oper-
ation. The dehumidifier has to stop oper-
ation.
Fill up with water and check that water
flows out of the drain outlet.
Fill up with water, start the dehumidifier
and check that the pump starts and emp-
ties the container.
Press to start dehumidifier and press to
switch off again.
Y
Y
Y
Y
Y
M
Is the water container ok?
Is the float working correctly?
Is the drain outlet from the drip tray ok?
Does the pump work correctly?
Control buttons:
Start/ stop