Preventive maintenance, cont.
Checklist (User)
- page 3
Acceptance: The filter is mounted. The
exhaust grille or exhaust plate
(S-
module) is mounted and fixed with 4
screws.
The grid within the exhaust air wholes on
the CDT 30S and CDT 40S are complete
and fixed.
Acceptance: The dehumidifier stops op-
eration after 10 sec.
Non-acceptance: The dehumidifier do n
ot
stop and continues operation.
Acceptance: Free passage through drain
outlet.
Acceptance: The pump starts and emp-
ties container.
Acceptance for starting: The dehumidifier
starts up after 2 sec.
Acceptance for switching off: The dehu-
midifier switches off after 2 sec.
Fill up with water and check that water is
not escaping the container.
Water container is removed
during op-
eration. The dehumidifier has to stop op-
eration.
Fill up with water and check that water
flows out of the drain outlet.
Fill up with water, start the dehumidifier
and check that the pump starts and emp-
ties the container.
Press to start
dehumidifier and press to
switch off again.
Front and rear grille
(function and fixation)
Is the water container ok?
Is the float working correctly?
Is the drain outlet from the drip tray ok?
Does the
pump work correctly?
Control buttons:
Start/ stop