Setpoints
Setpoints and factory settings are as follows:
Description
Factory setting
Min
Max
AUTO Demand-control (RH%)
45%
35%
65%
Automatic BYPASS-COOLING
Bypass Tmin
(Outdoor temperature (T1))
15ºC 8 ºC 15 ºC
Bypass Tmax
Extract air temperature (T3)
24 22/OF 30 ºC
Afterheater (Electrical or water based)
Supply air temperature (T2)
18 ºC
10/OF
35 ºC
Extract air temperature (T3)
OF
15 ºC
30 ºC
Room temperature (T5)
OF
15 ºC
30 ºC
Preheater
T1/SET PHE (Electric preheater)
-2 ºC
-2/OF
-10 ºC
T1/SET GTC (Geothermal preheat)
0 ºC
0 ºC
0 ºC
Fan settings
Fan OFSET (gear between respectively steps
1 → 2 and 2 → 3)
25 gears 10 gears 30 gears
MAX FAN speed (Step 4)
100%
As step 3
100%
Filter change interval
Filter period
180 days
90 days
360 days
Back to factory set-
tings
When the INSTALLER MENU is active the unit can be set “BACK TO FACTORY SETTING” by
pressing UP and CENTER simultaneously for 10 sec.